Surgex SX-20NE-RT Instrukcja Użytkownika

Przeglądaj online lub pobierz Instrukcja Użytkownika dla Akcesoria komputerowe Surgex SX-20NE-RT. SurgeX SX-20NE-RT User Manual Instrukcja obsługi

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 3
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 0
SurgeX
Installation Instructions
SX20-NE/RT
120 Volt Connections
The SurgeX SX20-NE/RT product is rated at a load capacity of 20 Amps and shall
be wired only by qualified Electricians using 12 Ga. conductors as specified in
Article 310 of the 1999 National Electric Code, as set forth in Table 310-13. Any
type of conductor suitable for use in wet or dry locations such as (but not limited
to) THHN, THHW, THW, THWN, or TW shall be considered acceptable if local
Code permits. The circuit to which the product is connected must be protected by a
20 Amp circuit breaker.
In order for the SurgeX circuitry to function properly, the unit must be installed
exactly as stated below. (Unit will not function without a Neutral connection
Connect the wires from the electrical service (line) to the terminal block labeled
‘Line’. Black to Line; White to Neutral; Ground to Ground
Connect the wires to the equipment (load) to the lower terminal block labeled
‘Load’. Black to Load; White to Neutral; Ground to Ground
Indicator Lights
There are two indicator lights on the front of the unit: a green Self-Test light and a
yellow Remote light. The green Self-Test light indicates that power is applied to
the unit and the internal surge protection circuitry is fully functional. The yellow
Remote light shows that the remote control is active and the AC power is on.
Przeglądanie stron 0
1 2 3

Podsumowanie treści

Strona 1 - Installation Instructions

SurgeX Installation Instructions SX20-NE/RT 120 Volt Connections The SurgeX SX20-NE/RT product is rated at a load capacity of 20 Amps and shall

Strona 2

Remote Control Connections CAUTION: Do not repeatedly turn the unit off—on—off—on with a heavy load connected. The ICE™ circuitry absorbs the inrush

Strona 3

Auxiliary Relay Contacts The auxiliary relay contacts, labeled REL CONT on the terminal block, provide a way to cascade units or to provide confirmat

Komentarze do niniejszej Instrukcji

Brak uwag